Firmware V1.41 V1
08.11.2022
13/219
•
•
•
•
•
•
•
2.3 Intended Use
This controller has been designed exclusively for the intended use:
The VS 3015 CT controller is designed for use as pack controller in commercial and industrial refrigeration
facilities in accordance with the scope of functions and in accordance with the environmental conditions
described in this operating manual.
Read the safety instructions and the instructions for installation and putting into service, operation and
maintenance. THEN start the commissioning and/or operation of the machine / system.
The safety and functionality of the machine / system are only guaranteed for this intended application.
Never use the machine / system, its components, control components or parts for any other purpose.
The system must not be put into operation until conformity with the applicable EU Directives has been
established for the entire system.
2.4 Five safety rules according to DGUV Regulation 3
The following rules must be strictly observed!
1. Disconnect:
The entire system to be worked on must be disconnected from the power supply at all poles.
2. Secure against reconnection:
Attach information signs to the disconnected operating equipment stating:
What has been disconnected.
Reason for the disconnection.
Name of the person who made the disconnection.
Reconnection must be prevented using a suitable lock (e.g. padlock).
3. Prove dead (authorised skilled personnel only):
Check voltmeter just before use.
Prove dead on all poles at the disconnection point.
Prove dead on all poles at the work area.
4. Ground and short-circuit:
All electrical parts at the work area
must be grounded and then short-
circuited
.
5. Cover or block off adjacent live parts:
If there is live equipment adjacent to the work area, it must be
covered using appropriate materials (e.g. insulation blankets / plates).
DANGER
Warning of dangerous electrical voltage!
Warning of dangerous electrical voltage! Danger of
electric shock!
Beware of a possible external power supply!
BEFORE
connecting and disconnecting it must be
checked that
no voltage is present
at the controller! Connections/plug connectors of the device may
only be plugged in, removed and/or wired when
no voltage is present
.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...