08.11.2022
128/219
3. Analogue compressor speed / fan speed correcting variable
A. Correcting variable output for fan speed
In the case of continuous control, a 0-10 V signal for the speed of the fans is output via the analogue output 2 of
the Modbus analogue module (terminals C2/2 see
Terminal assignment of the Modbus analogue module 0..10
B. Correcting variable for compressor speed output
In the case of compressor combined control, a 0-10 V signal for the speed of the speed-controlled NT
compressor is output via the analogue output 2 of the basic module (terminals 55/56).
The 0-10 V signal for the speed of the LT compressors is output via analogue output 1 of the basic module
(terminals 53/54). The 0-10 V signal for the speed of the parallel compressors (MP compressors) is output via
the analogue output 1 of the Modbus analogue module
Modbus analogue module 0..10 V DC
For the frequency converter, an adjustment of the operating point of the FC / speed controller must be made in
addition to the adjustment of the input to the reception of a 0-10 V signal. A request of the pack controller of 0 V
at the analogue output here means minimum speed; a request of 10 V means maximum speed. The FC / speed
Special precautions must be taken for the connection of these outputs; see
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...