Firmware V1.41 V1
08.11.2022
112/219
5.18.2 Daily Run Times, Switching Pulses and Switch-On Rates
As well as the operating hours, the run times, switching pulses of the compressors per day and the switch-on
rate (utilisation) of the pack are recorded daily and stored with date (menu 6-2). The data are archived in the
pack controller for a period of 32 days and the display is shown in hours and minutes.
The switch-on rate is calculated in accordance with the following formula and is displayed in percent
Switch-on rate: pack switch-on rate
L: sum of all compressor run time
s: number of available compressors
T
1
: current time
T
0
: day change