5.12.9 Monitoring of the Gas Cooler Outlet Temperature
The chapter
Gas cooler outlet temperature regulation
describes the existence of two gas cooler outlet
temperature sensors. These are monitored as follows.
Gas cooler outlet temperature sensor t
gk1
The Pt1000 temperature sensor is monitored for short circuits and interruption. The priority of the message
Meas err.gas.out
can be set in menu 3-7.
Gas cooler outlet temperature sensor t
gk2
The Pt1000 temperature sensor is monitored for short circuits and interruption. The priority of the message
Meas err.gas.out
can be set in menu 3-7.
Monitoring for plausibility of the gas cooler temperature
The gas cooler outlet temperature used for the regulation (t
gk2
is used as default; in the case of any measuring
circuit error, t
gk1
Temperature sensors for regulation
) should be in a specific range during
normal operation of the system. Two limit values are used for the range monitoring:
Parameters in menu 3-3:
tg too high
tg too low
In the event of exceeding
tg too high
, the signal
tg too high
is output after expiry of a configurable signal delay
time using the parameter
Del. tg too h.
(menu 3-3). The signal is transmitted according to priority preselection.
In the event of undercutting
tg too low
, the signal
tg too low
is output after expiry of a configurable signal delay
time using the parameter
Del. tg too l.
(menu 3-3). The signal is transmitted according to priority preselection. In
the case of measuring circuit errors of the temperature used for the fan control, the signals
tg too high
and
tg
too low
are not output.
The signals
tg too high
and
tg too low
have no influence on the control and regulation processes.
Содержание VS 3015 CT
Страница 46: ...Firmware V1 41 V1 08 11 2022 46 219...
Страница 52: ...Firmware V1 41 V1 08 11 2022 52 219 Number of gas ejectors 3 ejectors have the same size YES...
Страница 120: ...Firmware V1 41 V1 08 11 2022 120 219 No Function 1 2 3 4 SHIELD GROUND green CAN LOW brown CAN HIGH white...
Страница 159: ...Firmware V1 41 V1 08 11 2022 159 219 Display of the setpoint characteristic...