7.2.1 Assignment of the 230 V AC power supply
The connection is used for the power supply of the controller.
Connection:
Only on basic module - terminal block, upper right at the back
Terminal No. Function
Basic module
N, L, PE
230 V AC power supply (SUPPLY):
Neutral conductor, phase 230 V AC, PE (ground conductor)
Connection to the power supply
Connection cable requirements
As the controller is not equipped with an integrated disconnecting device in the form of a power switch, the
following must be implemented:
a) a switch or circuit breaker must be installed in the system or building installation,
b) this must be suitably positioned and easily accessible for the user, and
c) must be labelled as a disconnecting device for the equipment.
Warning of dangerous electrical voltage! Danger of electric shock! BEFORE
connecting and
disconnecting it must be checked that the 230 V AC power supply cable is
disconnected from the
power supply
! The controller is only permitted to be connected to the intended mains power supply!
In order to fuse the mains power line, a circuit breaker with the following characteristics is
recommended:
•
Rated current for 230 V AC:
6 A
•
Tripping characteristic (type):
B