Information for the precise terminal assignment can be found in chapter
5.3 Default parameter settings
The parameters listed below must be adjusted in the corresponding operating screens of the controller:
menu 3-1 -
System config
Refrigerant Z1 / Refrigerant Z2
- scroll using the cursor buttons (↓) (↑) and select the appropriate refrigerant.
Sensor match
The pack controller operates with continuous pressure transducers with linear characteristic. The
pressure inputs can be adjusted for various transducers with linear characteristic. Both transducers with
current output (4..20 mA) as well as those with voltage output (0…10 V) can be used here.
For transducers with voltage output, the corresponding jumpers must be implemented on the
controller (see chapter
)! Analogue
Configuration of the analogue inputs and outputs, page 90
inputs in the pack controller are preconfigured as current inputs (4..20 mA) at the factory.
The following parameters are used for matching the controller to the pressure transducer
1LP-Transducer and
HP-Transducer:
It must be selected here whether the transmitters have a current output or a voltage output.
2.
LP-Min
Parameter defining the pressure at which the LP transducer outputs the 4 mA or 0 V signal.
3.
LP-Max
Parameter defining the pressure at which the LP transducer outputs the 20 mA or 10 V signal.
4.
HP-Min
Parameter defining the pressure at which the HP transducer outputs the 4 mA or 0 V signal.
5.
HP-Max
Parameter defining the pressure at which the HP transducer outputs the 20 mA or 10 V signal.
No. Comps. Z1 and No. Comps. Z2
Number of compressors in Z1 and Z2
Anz. L-Stufen Z1 and Anz. L-Stufen Z2
Number of capacity stages in Z1 and Z2
AnzVerd.m.LS Z1 and AnzVerd.m.LS Z2
Number of capacity controlled compressors in Z1 and Z2
No. cond.stages
Number of condenser capacity stages
Menu
3-4 Comp. monitor
t0 OFF Comp. Z1 and t0 OFF Comp. Z2