KGL Operating Manual – VS 3010 BS
2018-07-02
/
107 178
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be ensured that
is present at all connections of the controller.
no voltage
Wiring of the digital inputs: All digital inputs of the SIOX extension module must be set to 230 V AC
for the operation.
If 230 V AC is applied to an input that has been configured for 24 V AC, this results in destruction of
the module.
6.2 Terminal diagrams for base module and SIOX
Base module in complete design with one SIOX extension module
6.2.1 Terminal assignment of the 230 V AC power supply
Connection: Only on base module – terminal block, upper right at the back