8.2.3.2 CI 3x00 store computer / AL 300 operator terminal - unlock
Before entering values, the input lock on the store computer or operator terminal must be deactivated as
follows:
Select menu item 9 "Parametrisation" in the main menu.
Step 1:
Step 2: Select menu item 3 "Lock-down" in this menu.
Step 3: A. Unlocking store computer (standard)Tap the
button (
) to set the marker (√). The lock-
ENTER
down has now been deactivated and it is possible to make settings. or B. Unlocking store computer and
Input current date backwards (nothing is shown on the
activating Superuser mode (Superuser permissions)
display).
The current date is April 17, 2016, i.e. 17/04/16; the required input for enabling Superuser
Example:
permissions is then 614071.
Confirm the input with the
button (
), an "S" is shown on the display.
ENTER
Step 4: Exit the operating screen and return to the main menu by tapping the ESC button twice.
Tip: If you are already in the user interface of a CAN bus node but have forgotten to deactivate the
input lock-down, you can unlock the input lock-down for this controller using the button combination
and . The entry block is active again as soon as you exit the user interface of the controller.
MODE
,
8.2.4 Activating service mode
For repair and maintenance work, service personnel can deactivate the remote alarm signalling function of the
system centre and of the store computer for a limited period using the service mode.
The service mode is exclusively reserved for service personnel! If there are still pending alarms (with
the priority 1..99) after the time for the service mode has elapsed, the audible warning devices and
the alarm relays are activated and the alarms are forwarded using the automatic transmission of
alarms.
8.2.4.1 CI 4x00 system centre service mode
Activating/deactivating service mode