Malfunctions due to interference! All supply lines from and to the controller (with the exception of the
230 V power supply and signal lines) must be shielded (cable type LiYCY)! This particularly applies
for the analogue inputs and outputs (e.g. sensor supply cables) as well as for the CAN bus cabling
(see
). As a general rule, care should be
Basics and General Safety and Connection Instructions
taken to ensure that signal cables and cables carrying mains voltage are routed in separate cable
channels.
Terminal No.
Function (0..10 V)
Base module
53
54
Speed controlled fan control
GND
+0..10 V
55
56
Speed controlled compressor control Z1
GND
+0..10 V
57
58
Speed controlled compressor control Z2
GND
+0..10 V
63
64
EEV cascade opening degree
GND
+0..10 V
6.2.6 Terminal assignment of CAN bus, SIOX and Modbus
Connection: On the base module and SIOX extension module – connections on the left side
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connecting and
disconnecting, it must be ensured that
is present at all connections of the controller.
no voltage
Danger of destruction of components! The connection of SIOX extension modules with each other or
to the controller may only be performed when no voltage is present! In the event of any mix-up of the
SIOX data cable (RJ45) with an Ethernet network cable with PoE (Power over Ethernet), involved
network devices can be damaged!