Firmware V7.16.x
16.05.2023
84/183
7.2 SIOX extension module terminal diagram
The following figure shows a SIOX (
S
erial
IO
E
x
tension) extension module with switches.
The description of the connection and terminal assignments for the digital inputs, the relay outputs and the
SIOX interface is provided on the following pages. For detailed information about the connection, configuration
and special features of the SIOX extension module, see chapter
DIN rail mounting - SIOX Extension Module
.
•
•
•
•
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock or
malfunction!
The following points must be
strictly
observed for the cabling:
Before
detaching or inserting plug contacts on the extension module, the system must be
disconnected from the power supply
!
To
protect stripped wires,
the use of wire end ferrules with plastic collars is mandatory on
all
COMBICON mating connectors for
230 V AC
!
In order to guarantee reverse polarity protection, only coded mating connectors may be used on the
connectors of the assembly.
All
connection cables
from and to the extension module - with the exception of the relay outputs
and the digital inputs - must be
shielded
. Otherwise malfunctions, e.g. faulty measurements,
cannot be ruled out.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...