Firmware V7.16.x
16.05.2023
35/183
5.6.3 Relay outputs for week timers
By using up to a maximum of 4 SIOX extension modules (see chapter
SIOX - connection to the controller
), the
number of relay outputs can be increased by another 32 (8 relay outputs for each SIOX module, see Menu
4-1-1). Depending on the configuration and programming, the number of relay outputs can be even further
increased by using a GLT / DDC controller.
Configuration
Week timers with up to 7 control times (see Menu 4-1-4) can be configured for each relay output. The control
times can be set accurate to the minute and on individual weekdays or weekday groups.
Control times
authorised time period
Weekday
Mon, Tue, Wed, Thu, Fri, Sat, Sun
0:00 - 23:59
Weekday
groups
Mon-Fri, Mon-Sat, Sat-Sun
Start earliest 0:00
End latest 23:59, but not until after start time
The following applies: start time < end time
Control times over a day change are
not
authorised:
Example:
Start 21:00
End 07:00!
Mon-Sun (1 week)
0:00 - 23:59
Control times over a day change are authorised:
Example:
Start 20:00
End 08:00
In addition to the switching output, a passing contact, either as an alternative or in addition, can be defined for
each relay output. The passing contacts switch on simultaneously with the switching output and switch off again
after a duration of approx. 5 seconds. For connection details, see chapter
If the week timer should go over a day change (e.g. 20:00 - 8:00), it is only possible with individual
days, e.g. Mon 20:00 - 23:59 and Tue 0:00 - 8:00 or with the Mon-Sun weekday group as 20:00 - 8:00!
Individual control times are also permitted to overlap:
1. Week timer Mon-Sun 20:00 - 08:00
2. Week timer Sun 00:00 - 23:59
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...