KGL Operating Manual – UA 412 S
2019-01-14
/
59 122
The USB A-B cable can now be disconnected from the controller.
Step 3: Reset DIP switch S3
After performing a firmware update,
the coding switch 9 of the DIP switch S3
:
only
must be reset to ON
Risk of controller failure! The controller only accepts the settings for DIP switch S3
the controller
after
has been briefly disconnected from the power supply!
After the firmware update, the saved settings can be reloaded into the case controller from LDSWin
as required..
6.9.2.2 Update for controller with 8-pole DIP switch
Controller characteristic: 8-pole DIP switch
The settings depend on the controller type!
The steps described in the chapter
must have
Voraussetzungen für das Firmware-Update, page 54
been performed once for each PC in order to perform a successful firmware update.
Step 1: Set DIP switch S3 and connect controller to PC
Practical tip: The original position of the coding switches 1..8 of the DIP switch S3 should be
documented, e.g. with a mobile telephone photo.
Before starting the firmware update, all coding switches 1..8 of the DIP switch S3
be set to
:
must
ON