KGL Operating Manual – UA 412 S
2019-01-14
/
89 122
RAHMEN XXXXX
Frame heater xxx
Display current ON / OFF state of the frame heater output terminals 91/92
Einschaltdauer xxx %
Display current run time of the frame heater
Feuchte XXX%
Display current room humidity (transmitted via CAN nus from the VS using the installed humidity sensor)
Raum-Temp xx °C
Display current room temperature (transmitted via CAN nus from the VS using the installed room temperature sensor)
9.1.3 Menu 2 Setpoints
SOLLWERTE POS: XXXXX
1 Cooling
Continue to menu 2-1
2 Defrost
Continue to menu 2-2
3
Not applicable for this controller type
4 Alarm
Continue to menu 2-4
5 Frame heater
Continue to menu 2-5
Menu 2-1 Cooling
KÜHLUNG POS: XXXXX
1 Setpoints
Continue to menu 2-1-1
2 Sollwerte Umsch.
Continue to menu 2-1-2
is not displayed when toggle setpoint is deactivated (menu 3-3)
Menu 2-1-1 Setpoints
KÜHLUNG POS: XXXXX
Input
Default
Setpoint R2 xxx °C
Setpoint supply air temperature
-10..20
-2 °C
Hysteresis R2 X K
Setpoint hysteresis supply air temperature
1..8
4 K
Setpoint R4 XXX °C
Setpoint return air temperature
-10..20
6 °C
Hysteresis R4 X K
Setpoint hysteresis return air temperature
1..8
2 K
Menu 2-1-2 Sollwerte Umsch.
KÜHLUNG POS: XXXXX
Input
Default
Setpoint R2 xxx °C
Setpoint supply air temperature
-10..20
-4 °C
Hysteresis R2 X K
Setpoint hysteresis supply air temperature
1..8
4 K
Setpoint R4 xxx °C
Setpoint return air temperature
-10..20
5 °C
Hysteresis R4 X K
Setpoint hysteresis return air temperature
1..8
4 K
Menu 2-2 Defrost
ABTAUUNG POS: XXXXX
Input
1 Setpoints
Continue to menu 2-2-1
1
2 Sollwerte Umsch.
Continue to menu 2-2-2
is only displayed if two-zone operation is set (menu 6-1)
2
Menu 2-1-1 Setpoints
ABTAUUNG POS: XXXXX
Input
Default
Abtauendtemp XX °C
Setpoint defrost end temperature
--, 0..20
10 °C