KGL Operating Manual – UA 412 S
2019-01-14
/
51 122
3 Clock - 3 Toggle Setpoint
Sollumschaltg. EXT
Selection INT, EXT, --: internal, external, deactivated toggle setpoint
Selection
INT: internal
EXT: external
--: deactivated toggle setpoint
Laufzeit Rollo 0s
Input operating time of the blind of the multidecks
For ON: DD-DD hh:mm
Input time for toggle setpoint
(only visible if Sollumschaltg. is set to INT)
For OFF: DD-DD hh:mm
For ON: DD-DD hh:mm
For OFF: DD-DD hh:mm
10. Tap the
button twice to exit the menu
.
ESC
3 Toggle Setpoint
11. Return to the main menu of the store computer / operator terminal by tapping the
button multiple
ESC
times.
12. Select the menu
in the main menu of the store computer / operator terminal
7 Monitoring - 3 Configuration
and input, among other things, the node name of the case controller in plain text.
7 Monitoring - 3
Configuration
KONFIGURATION
Kn.nnn
Input of the CAN bus address: Select the case controller with the corresponding CAN bus address (node No. = 1..99) to be
parametrised using the cursor or by direct input.
Teilnehmername
Input node name (e.g. Cheese Counter)
Position XXXXX
Input of the position of the node in the store
Priorität X
Input of the desired priority
13. Ending basic configuration of the controller
Tap the
button multiple times to return to the main menu. This ends the basic configuration.
ESC
6.7 Naming the controller
The following parameters are available for naming the controller:
- refrigeration point name (19 characters, can be freely edited)
- refrigeration point position (5 characters, can be freely edited)
The controller can be named using the system centre, store computer, operator terminal or the PC software
LDSWin.
The input is made in menu 6-1.
A. BT 300 operator interface
Any naming of the controller with a BT 300 x operator interface is only possible for the UA 410 L
controller.
B. System centre For details, see chapter