5.12 Emergency power operation
Function
The aim of the emergency power operation is, in the event of an interruption in the power supply, to provide
intelligent support for the emergency power supplied via an emergency generating unit. The LDS components
are designed to prevent unnecessary power consumption which could endanger the emergency power supply.
If the allocated pack controller detects an interruption in the power supply then this is transmitted to the case
controllers via the CAN bus. In combination with the emergency power operation functions, the case controllers
can block control functions as required. This serves to reduce the load on the emergency generating unit.
Activation of emergency power operation
The participation of the case controllers in the emergency power operation can be set individually. To do this it
is necessary to specify the allocated pack controller via menu item 6-1 on the case controller. This pack
controller must support emergency power operation and be parameterized accordingly in order for it to dispatch
an emergency power message (see the pack controller operating instruction).
The behaviour of the case controller in emergency power operation can be set using the following parameters
in menu 6-6:
Cooling functionality Parameter Cool.funct.OFF
Defrost functionality Parameter Defr.funct.OFF
Fan functionality Parameter Fan funct. OFF
Frame heating functionality Parameter Frame fct.OFF
Light functionality Parameter Light fct.OFF
If, for example, the case controller is required to switch off the cooling on receiving an emergency power
message, then the parameter
Cool.funct.OFF
must be set to Y (Yes). If this parameter is set to N (No), then the
case controller continues cooling even during emergency power operation.
All other parameters in principle function the same. They determine whether the defrosting or the fan is
switched off during emergency power operation. If the controller is conducting a defrost at the start of
emergency power operation then the defrost is immediately interrupted. If the defrost command comes during
emergency power operation then the command is ignored.
Defrosts that are ignored or interrupted due to emergency power operation are not automatically
repeated by the controller. If a defrost interruption occurs due to emergency power operation then the
refrigeration capacity of the corresponding refrigeration points must be checked.
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...