Firmware V3.15
21.04.2021
16/401
•
•
•
•
•
•
•
•
•
•
•
•
3.2 Hardware
The case controller is housed in a plastic casing for DIN rail mounting and does not require any further optional
expansion modules. Up to 99 case controllers can be used within the LDS system. As required, a BT 300 x
Operator Interface and up to 4 BT 30 Temperature Displays can be connected. For the direct parameterisation
via LDSWin or for a firmware update, the controller can be connected to a laptop or PC via the USB interface.
The application range of the case controller is described in more detail in
The following diagram illustrates the system architecture of the UA 410 AC case controller (complete):
Ports
CAN bus: Communication in E*LDS-System, new version
DISPLAY: Connection for BT 300x Operator Interface and up to four BT 30 Temperature Displays
CI 320: Communication with LDSWin software / Connection to the legacy system CI 320
USB: For conducting a firmware update
Inputs/outputs
4 digital inputs 230 V AC, floating
10 analog inputs Connection for two-wire NTC temperature sensors
Only UA 410 AC:2 x analogue inputs 4..20 mA - currently without function
Outputs
3 relay output 230 V AC / 6 A (changeover)
4 relay outputs 230 V AC / 6 A (N.O.)
2 transistor outputs 24 V DC / 50 mA (for lighting control and frame heater)
Only UA 410 AC:2 x analogue outputs 0..10 V DC - currently without function
Real-time clock
Only UA 400 AC: Battery-backed, lithium cell
For precise details of the different features of the controllers UA 400 CC and UA 400 AC
see
chapter
. The connection and terminal configurations are described in
the
Pin and Terminal Assignments of UA 400
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1 ...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button ...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD ...
Страница 244: ...Firmware V3 15 21 04 2021 244 401 ...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint ...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay ...
Страница 372: ...Firmware V3 15 21 04 2021 372 401 ...