Firmware V3.15
21.04.2021
23/401
5.2.1 Necessary and optional sensors
Depending on the controller type and the operating mode (single-zone operation / two-zone operation), there
are necessary and optional temperature sensors for the case controller. A sensor scan is performed
automatically during
Erstanlauf - Regler auf Werkseinstellungen zurücksetzen
of the controller. The number of
scanned sensors can be checked in the menu (6-1) or with the LDSWin PC software. This allows unconnected
sensors to be removed from the monitoring for sensor fault.
The following list shows the necessary and optional temperate sensors for the regulation.
Controller type
Sensors necessary for regulation
Optional sensors
(advanced functions)
Single-zone operation
UA 111 / UA 141
R2.1
R2.2 R2.3 R2.4 R4.1 R4.2 R4.3 R4.4
UA 121 / UA 131 / UA 131 LS
R1.1 R2.1
R1.2 R1.3 R1.4 R2.3 R4.1 R4.2 R4.3 R4.4
UR 141 NK
R4.1
R1.1 R1.2 R1.3 R2.1 R2.3 R1.4 R4.2 R4.3
R4.4
UR 141 TK
R1.1 R4.1
R1.2 R1.3 R1.4 R2.1 R2.3 R4.2 R4.3 R4.4
UA 111 D
R2.1
R2.2 R2.3 R2.4 R2.5 R4.1 R4.2 R4.3 R4.4
R4.5
UA 131 DD
–
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.1 R4.2
R4.3 R4.4
Two-zone operation
UA 111 / UA 141
R2.1 R2.3
R2.2 R2.4 R4.1 R4.2 R4.3 R4.4
UA 121 / UA 131 / UA 131 LS
R1.1 R1.3 R2.1 R2.3
R1.2 R1.4 R4.1 R4.2 R4.3 R4.4
UR 141 NK
R4.1 R4.3
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.2 R4.4
UR 141 TK
R1.1 R1.3 R4.1 R4.3
R1.2 R1.4 R2.1 R2.3 R4.2 R4.4
UA 111 D
Not applicable as controller type does not support
two-zone operation
UA 131 DD
–
R1.1 R1.2 R1.3 R1.4 R2.1 R2.3 R4.1 R4.2
R4.3 R4.4
Содержание UA 400
Страница 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Страница 133: ...Firmware V3 15 21 04 2021 133 401 Upper case and lower case can be toggled by tapping the MODE button...
Страница 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Страница 244: ...Firmware V3 15 21 04 2021 244 401...
Страница 324: ...Firmware V3 15 21 04 2021 324 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 357: ...Firmware V3 15 21 04 2021 357 401 COOLING 1 Pos XXXXX Hystersis R4 1 xxx K Supply air temperature hysteresis setpoint...
Страница 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Страница 372: ...Firmware V3 15 21 04 2021 372 401...
Страница 399: ...Firmware V3 15 21 04 2021 399 401 12 2 Mechanical Data DIN rail mounting A Connector set with cable All dimensions in mm...