Firmware: V2.18 / V--
26.10.2022
42/119
1.
2.
3.
6.1 Formal structure of the Signal List
The Signal List must have a certain formal structure so that the Signal List Tool can generate the source code
files for CODESYS and the GLT Config for the system centre without errors:
The first cell in Excel,
A1
, must contain the marker $$ so that the following functions are available.
There are markers in
row 1
that indicate the function of the relevant columns. This means that the meaning
of the information can be distributed to the columns as desired.
The area containing valid data is framed by the abbreviations $START and $ENDE.
The following screenshot shows an extract from the beginning of a Signal List:
Содержание Compact GLT 3010
Страница 90: ...Firmware V2 18 V 26 10 2022 90 119 10 2 Connections for 230 V AC top Base module SIOX Extension Module ...
Страница 99: ...Firmware V2 18 V 26 10 2022 99 119 10 3 Connections for safety extra low voltage bottom ...
Страница 104: ...Firmware V2 18 V 26 10 2022 104 119 10 4 Connections for interfaces on the side Base module SIOX Extension Module ...