Installation and Startup of Combi Gateway
37
Version 1.6 04. November 2016
6.6.4
Modbus-TCP-Master-Gateway
The Modbus-TCP-Master-Gateway software module is not enabled until activation with a valid activation code;
see chapter 6.6.1.3. Up to four Modbus-TCP-Master gateways can be integrated in the E*LDS system.
The individual gateways 1..4 are configured under the corresponding tabs
Modbus-Gateway 1 to Master-Gateway 4:
The settings of the respective Modbus-TCP-Master-Gateways 1..4 are made
using the
Basic configuration
,
CAN bus
and
Alarm
tabs on the bottom left.
Basic configuration
The specific parameters of the Modbus-TCP-Master gateway are set in the basic configuration. The activation
of the Modbus-TCP-Master process is controlled by the ”Active” checkbox. If the process is deactivated, this has
the consequence that the external data points are no longer mapped in the E*LDS system and the functions of
the Modbus-TCP-Master cannot be used.
More detailed descriptions of the tasks and functions of this software module
are available in the separate ”Modbus-TCP-Master-Gateway” API documentation.
If the external data points of an external system are mapped to the process image in the E*LDS system, the
E*LDS system can be used, for example, for monitoring purposes of external systems. A configuration file which
specifies the mapping is saved for this. Further information about the structure of the configuration file is avail
able from the manufacturer.
A manual system restart is required to apply the changes of the configuration; see chapter 6.6.1.3.
Содержание Combi
Страница 1: ...Version 1 6 04 November 2016 Operating instruction Combi Gateway Version V1 57 ...
Страница 6: ...iv Version 1 6 04 November 2016 Notice ...
Страница 18: ...Application Combi Gateway 12 Version 1 6 04 November 2016 Notice ...
Страница 54: ...Decommissioning and disposal 48 Version 1 6 04 November 2016 Notice ...
Страница 58: ...Order No s and accessories 52 Version 1 6 04 November 2016 Notice ...