Installation and Startup of Combi Gateway
23
Version 1.6 04. November 2016
6.4
Starting Combi Gateway
During the start-up of the Combi Gateway messages are shown in the 7-segment display.
Sequence during
start-up
7-segment
display
Discription
1. Start-up
0... 1... 2... 3
Display of 0, 1, 2, 3, the controller is booting
cycling
2. Information
on USB stick
and
configuration file
c o n f - s n f
c o n f - f n f
c o n f - e r r
c o n f - s u c
The following information is displayed following “conf” (configuration):
snf
Stick not found – USB stick is not recognized.
Cause: The USB stick has not been plugged in, or
the plugged USB stick is not recognised, i.e. supported.
fnf
File not found – A USB stick has been recognised, but no configuration file.
Cause: The file cannot be found on the USB stick,
see chapter NO TAG.
err
Error – Faulty data, no changes have been made.
Cause: At least one data point within the configuration file
is outside the valid value range, see chapter 6.5.1.1.
suc
Success – The configuration file has been successfully read and used.
cycling
3. Infomation
on the
IP configuration
IP-
xxx.xxx.xxx.xxx
Display of the IP address:
The IP address is displayed with the four xxx numbers separated by a point.
4. Standard
operating mode
cycling
The Combi-Gateway is in standard operating mode.
Display of error
messages
E -- 0 - 2
E -- 0 - 6
E -- 4 - 5
E -- 6 - 0
Two-digit error code, see chapter 6.4.2
The 7−segment display begins to cycle when operational readiness is reached. This process can last up to 5
minutes. The standard operating mode of the Combi Gateway displays the following messages:
7-segment display:
circling
LED 2:
:
ON
In case of an error a two digit error code will be displayed,
see chapter 6.4.2 for detailed information.
The LED labelled
LED 2
indicates that the Combi Gateway is able to communicate with the store computer of
the E*LDS System. The LAN gateway is now included in the monitoring of the system’s CAN bus komponents
and is subject to failure monitoring by the store computer (alternatively: operator terminal), see chapter 6.4.1.
Содержание Combi
Страница 1: ...Version 1 6 04 November 2016 Operating instruction Combi Gateway Version V1 57 ...
Страница 6: ...iv Version 1 6 04 November 2016 Notice ...
Страница 18: ...Application Combi Gateway 12 Version 1 6 04 November 2016 Notice ...
Страница 54: ...Decommissioning and disposal 48 Version 1 6 04 November 2016 Notice ...
Страница 58: ...Order No s and accessories 52 Version 1 6 04 November 2016 Notice ...