Firmware V6.6.9
29.07.2020
64/147
7.1.5 Terminal assignment of the SIOX interfaces
The interfaces for the connection of up to 4 SIOX extension modules to the system centre are located on the
device at the bottom. The number (1..4) of extension modules is defined in Menu 4-1-1. With each additional
SIOX, the system centre is extended by 12
(e.g. for system monitoring or for energy meters) and 8
(e.g. week timers or for load shedding).
Terminal No.
Function
Power supply - SIOX SUPPLY *
91
92
93
94
95
Ground of 9 V
+9 V DC
Ground of 24 V
+24 V DC
SHLD (shield)
Data port - SIOX OUT *
RJ45 female connector
Data cable output for the connection
of the first SIOX extension module
* Recommendation:
SIOX supply cables and SIOX data cables are available as accessories for the
connection, see chapter
.Accessories for system centre v6.0
.
7.1.6 Terminal assignment of the COM3 / Modbus terminals (RS485)
Only CI 4100 or higher:
The connection is used for connecting UA 30 / Dixell controllers and LDS1 gateways in the E*LDS system and
is located on the left side of the device. The COM3 / MODBUS interface is configured in Menu 4-1-5.
Danger of destruction of components!
SIOX extension modules may only be connected to each
other or the system centre when
no voltage is present
! In the event of an Ethernet network cable with
PoE (Power over Ethernet) being used instead of the SIOX data cable (RJ45) damage can occur to
participating network devices! Only components approved by Eckelmann AG may be connected to the
SIOX extension bus (terminals SIOX OUT / SIOX IN or terminals 91..95)!