5.5 Selection of the sensor type
The case controller uses 2-wire NTC temperature sensors for the regulation. For the variants UA 400 E CC / UA
401 E CC / UA 410 E AC, 5 sensors (Z1..Z5 for single-zone operation) can be connected, for the variants UA
400 E CC / UA 410 E AC, 10 sensors (Z1..Z5 / Z6..Z10) can be connected for two-zone operation).
UA 410 E AC (complete design)
All connected sensors
must
be identical in their type and are not parametrised individually. The type of the
sensor can be set with the parameter
Fühlertyp
(menu 6-2-5). For details, see chapter
the analogue inputs for temperature sensors
The following NTC sensors are intended:
L243 (K243) - temperature range -50 .. 50 °C
The sensor K243 can also be used instead of the sensor L243. The characteristic curves of these two
sensors are identical.
K277 - temperature range -50 .. 50 °C
5K3A1 - temperature range 0 .. 100 °C
For detailed information and dimension details, see chapter
Mechanical data of the temperature sensors L243 /
ATTENTION
The sensors must be mounted carefully. If sensor cables are exclusively laid within the refrigerated
case to be monitored, and sources of interference (for example parallel power lines) are not
anticipated, then it is possible to dispense with shielding. Otherwise, interference in the sensor cables
must be prevented using suitable measures.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...