Firmware V3.13
21.04.2021
46/466
5.7.4 Continuous temperature control by coldroom sensor
Controller types UR 141 TE, UR 141 NE
Cooling is controlled according to temperature measured on the cold room air sensor. When cold room air
temperature equals the current setpoint, opening duration of the expansion valve is reduced to the time
required to maintain the current state. Cooling can take place in single-zone mode or two-zone operating mode.
In single zone mode, Ry.1 sensors act on Relay 1.
R4.1: Cold room air sensor (Terminal Z21/22)
R5.1: Evaporator inlet sensor (Terminal Z41/42)
R6.1: Evaporator outlet sensor (Terminal Z51/52)
Expansion valve 1: Relay for expansion valve 1 (Terminal 23/24)
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...