Pin and Terminal Assignments of AL 300
24
Version 3-1 05. Dezember 2019
5.1.1
Terminal assignment for 230 V AC power supply
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked
that the 230 V AC supply cable is
off load
!
Terminal No.
Function
L, N PE
Power supply 230 V AC (
SUPPLY
):
Phase 230 V AC, neutral conductor, ground conductor
5.1.2
Terminal assignment for 230 V AC relay outputs
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked
that the 230 V AC relay outputs are
off load
!
Low voltage
and
safety extra-low voltage must
not
be applied together
at the relay outputs 15/16/18, 25/26/28 and 35/36/38.
Terminal No.
Function
15 (common)
16 (N.C.)
18 (N.O.)
Horn
25 (common)
26 (contact closed by alarm)
28 (contact opened by alarm)
Alarm output Priority 2 (PRIO.2)
35 (common)
36 (contact closed by alarm)
38 (contact opened by alarm)
Alarm output Priority 1 (PRIO.1)
Light switch
(for switching of a protective circuit breaker)
1, 2
For switching of contactor with suppressor (
LIGHT
)
5.1.3
Terminal assignment for 230 V AC digital inputs
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked
that the 230 V AC digital inputs are off load!
Terminal No.
Function
A1, A2
Alarm input 1
(AL.1), 230 V AC (floating)
B1, B2
Alarm input 2 (AL.2), 230 V AC (floating)
Содержание AL 300 S
Страница 21: ...Function of AL 300 16 Version 3 1 05 Dezember 2019 Notice ...
Страница 31: ...Pin and Terminal Assignments of AL 300 26 Version 3 1 05 Dezember 2019 Notice ...
Страница 51: ...Decommissioning and disposal 46 Version 3 1 05 Dezember 2019 Notice ...
Страница 59: ...Specifications of AL 300 54 Version 3 1 05 Dezember 2019 Notice ...
Страница 61: ...Order numbers and accessories of AL 300 56 Version 3 1 05 Dezember 2019 Notice ...