Installation and Startup of AL 300
19
Version 3-1 05. Dezember 2019
4.4
Restart - restart of the controller
For a restart, the device is restarted with all configured parameters and the CAN bus address set on the rotary
switch. A restart can be initiated using the following procedure:
- disconnection and reconnection of the power supply or
- by simultaneously pressing the buttons
MODE + ESC + 8
4.5
First start - load factory settings
During a first start, all parameters are replaced by the factory settings in the device; all previous settings are
deleted and lost. A first start can be initiated using the following procedure:
- by simultaneously pressing the buttons
MODE + ESC + 9
4.6
Special functions for startup
A number of special functions can be accessed by key combinations:
‐ triggering a test alarm with the priority X1..X9 by simultaneously pressing the buttons
MODE + 1..9
Note: test alarms are only triggered locally at the operator terminal and are used for testing the alarm wiring
at its relay outputs.
‐ triggering of a restart by simultaneously pressing the buttons
MODE + ESC + 8
‐ triggering of a first start by simultaneously pressing the buttons
MODE + ESC + 9