Version 3-1 05. Dezember 2019
4.2
Wall mounting of AL 300 W
Type AL 300 W Operator Terminal for wall mounting is housed in a plastic casing. The power consumption of
the Operator Terminal is 5 VA.
See Section “Specifications” for electrical enclosure, measurements and panel mounting cut-out.
See the Pin and Terminal Assignments chapter for wiring details.
4.3
Setting the CAN bus address
Use the rotary switch on the left of the COM port to set the CAN bus address:
5
0
2
3
1
4
6
7
8
9
ZNR.
51203
68
830
DEF0
PE L N
COM
A unique CAN bus address (Node No. 112 to 120) must be assigned to each AL 300 Operator Ter
minal (maximum nine terminals).
Switch position
CAN bus address
Function
0
-
CAN bus communication in AL 300 Operator Terminal deactivated.
1 .. 9
112 .. 120
Normal operating mode.
If the system centre / store computer fails or is switched off, the AL 300 Operator Terminal (if
present) with the lowest CAN bus address takes over the monitoring for the duration of the discon
nection.
After changing the switch position, the AL 300 Operator Terminal MUST be disconnected briefly
from power or restart must be performed by simultaneously pressing the
MODE + ECS + 8
keys for
the new settings to take effect!
Содержание AL 300 S
Страница 21: ...Function of AL 300 16 Version 3 1 05 Dezember 2019 Notice ...
Страница 31: ...Pin and Terminal Assignments of AL 300 26 Version 3 1 05 Dezember 2019 Notice ...
Страница 51: ...Decommissioning and disposal 46 Version 3 1 05 Dezember 2019 Notice ...
Страница 59: ...Specifications of AL 300 54 Version 3 1 05 Dezember 2019 Notice ...
Страница 61: ...Order numbers and accessories of AL 300 56 Version 3 1 05 Dezember 2019 Notice ...