Function of AL 300
15
Version 3-1 05. Dezember 2019
3.5
Alarm suppression in manual shutdown of case controllers
Shutdown of a refrigerated case or coldroom is detected by CAN bus station monitoring as a failure (Screen 7-1).
The display of all AL 300 and - if present - of the CI 4x00 System Centre or of the CI 3000 / CI 3100 Store Computer
then shows the query whether the refrigeration point has been deliberately unloaded.
The user can then confirm shutdown within 5 minutes by pressing ENTER.
If confirmation is made within this interval, monitoring of the case or coldroom concerned will be deactivated
and accordingly it will
not
be reported as a failure.
Otherwise, or if the user answers no to the prompt by pressing the ESC key, the case or coldroom will as nor
mal be reported as failed. A case or coldroom that has been shut down is automatically re-included in station
monitoring when it is switched on again.
Any disconnection of refrigeration points is registered in the message list of the system centre /
store computer (if this is present)!