XDM-300 Installation and
Maintenance Manual
Equipment
Installation
417006-2311-0H3-A00 ECI
Telecom
Ltd.
Proprietary
3-39
Installing the OPP
The OPP can be installed in the same rack as the XDM-300 or in other racks
according to the site installation requirements.
To mount the OPP in the rack:
1.
Attach the OPP to the rack rails and secure it using the four supplied
screws, washers, and nuts.
2.
Prepare the necessary fibers according to the site cabling diagram and the
detailed cabling diagrams or tables of each shelf. When preparing the fiber,
follow the safety information appearing in Work and Equipment Safety.
3.
Label the fibers in accordance with the cabling diagrams or tables.
4.
Thread the optical fibers into the conduits running along the front supports
of the ETSI A rack, or the rack sidewalls in case of an ETSI B rack.
5.
Push the button on the front panel of the OPP to release the latch, and pull
the OPP towards you to open it.
N
OTE
:
The OPP has two opening positions. The tray latches
with a click at the halfway position. Pull it again to open it
fully so that you can thread the fibers.
6.
Thread the fibers into the OPP, as illustrated in Threading and connecting
optical fibers in the OPP (on page
N
OTE
:
All optical fibers should be arranged in groups inside
the OPP, and fastened with Velcro strips.
7.
Identify the duplex connector position on the duplex connectors panel (on
page
).
8.
Connect each equipment fiber to the corresponding network fiber according
to the site cabling diagram and the detailed cabling diagrams or tables of
each shelf.
9.
Run the fibers up to the level of the corresponding optical connector.
10.
Return the OPP to the rack until it latches in place with a click.