background image

Product Overview

The TAP Task Ambient Photosensor monitors light levels

within interior spaces and transmits the value to lighting

controllers.

The TAP measures ambient light in two ranges: 0-510 lux

(0 - 47 foot candles) and 0-1024 lux (0 - 95 foot candles)

and is intended for indoor use only.

The package includes the TAP light sensor and installation

guide.

NOTE: The TAP is a solar powered device that

absorbs solar energy storing it for use during low

light periods. Before assigning the TAP device to a

receiver/controller, the device must be exposed to a

good light source for a minimum of 2 hours.

NOTE: The radio is protected by a sealed screw.

Breaking this seal will void the warranty.

Preparing to Install

Even with a brief exposure to light the TAP will operate

however, for best results the sensor should be mounted in

a location with exposure to light on a daily basis. The TAP

can be mounted on any surface; ceiling, wall, desk, cubicle

wall, etc.

The TAP sensor should be placed so there is direct

exposure to a window. The most common mounting

location for photo sensors is ceiling mount, centered with

the window, about 4' from the window. The TAP must be

installed in the space where the receiving lighting

controller is operating the light fixtures. There are online

software tools that can also assist in identifying the optimal

location to mount photo sensors. The TAP sensor can be

mounted using screws (not supplied) through the back

plate or using double sided tape or Velcro™ (not supplied).

1.) Attach the tape or Velcro to the back surface using two

pieces, each about 4cm. (1.5in.) in length. Insure none of

the tape will hang outside the sensors edges once

mounted.

2.) If you're using tape, remove the protective film to

reveal the sticky surface. If you are using Velcro, remove

the backing tape from the mating strip but do not separate

the Velcro strips.

3. Hold the sensor over the mounting location and gently

press to adhere.

The alternative method is to secure the photosensor with

screws and anchors (not supplied).

1.) Using a fingernail or small flat head screwdriver, pop

Wireless Solar Powered
Task Ambient Photo-
Sensor Installation
Guide

This guide covers model TAP-17 and TAP-17C.

Specifications subject to change without notice.

The model TAP-17C is equipped with an EnOcean 315MHz

radio and the TAP-17 model has the EnOcean 868MHz

radio.

Echoflex Solutions, Inc.

# 1, 38924 Queens Way

Squamish, British Columbia
Canada V8B 0K8
Toll Free: (888) 324-6359
[email protected]
www.echoflexsolutions.com

Copyright 2011-2012 Echoflex Solutions, Inc.
Specifications subject to change without notice.
Part # 8DC-5036 | Revision 1.7

FCC Part 15.231 (315MHz models only)

IC RSS-210: (315MHz models only)

Contains FCC ID: XMG-STM112C

The enclosed device complies with Part 15 of

the FCC Rules.

Operation is subject to the following two conditions:

(I.) this device may not cause harmful interference and

(ii.) this device must accept any interference received,

including interference that may cause undesired operation.

Contains IC: 72561A-STM112C

1

Отзывы: