Echoflex Installation Guide
Ceiling Vacancy-Occupancy Sensor
Lens Masking
Peel and stick lens mask
Lens mask stickers are provided to block a
section of the lens from detecting
occupancy. To attach, remove the backing
and stick the mask on the sensor lens to
cover the target section. Cut to size, if
required.
Link to a Controller
The target controller must be installed,
powered, and within range of the RVS RCS.
Repeating the linking process can also be used to unlink the device.
Teach button
Battery holder
1. Remove the cover to access the
[Teach]
button, using your fingers
to flex it gently and release the
tabs that hold it in place. If you
have difficulty, consider inserting a
small flatblade screwdriver under a
release tab.
2. Press the
[Learn]
button on the
controller to activate Link mode. If
necessary, refer to the controller product documentation.
3. Press the
[Teach]
button on the RVS RCS once to send a message. An
LED blinks to confirm a successful transmission.
4. Deactivate Link mode on the controller before attempting to link to
any other controllers.
Battery Power
A CR1632 battery is not required for normal operation of RVS models if
the sensor receives adequate natural or artificial light. See the table in the
Light Level Test on the next page
. A battery may be required to run
installation tests or when the artificial light is insufficient to power the
sensor.
A CR1632 is included with RCS models. The battery may be factory
installed or packed separately according to shipping regulations. Insert
the battery if required or remove the protective plastic tab before
installing the RVS RCS.
Note:
When the sensor transmits a message, the LED blinks. The
LED color indicates the battery's strength: green if good, blue if
low, and red if dead or missing.
Ceiling Vacancy-Occupancy Sensor
Page 5 of 12
Echoflex