background image

Echoflex Installation Guide

Ceiling Vacancy-Occupancy Sensor RVS RCS

Corporate Headquarters

n

Middleton, WI, USA

|

+1 608 831 4116

Web

echoflexsolutions.com

|

Email

[email protected]

|

Support

[email protected]

©2022 Echoflex Solutions, Inc. Trademark and patent info: 

echoflexsolutions.com/ip

Product information and specifications subject to change.
Echoflex intends this document to be provided in its entirety.

8188M2102

Rev B Released 2022-04

Overview

Dual-tech model shown

The wireless Ceiling Vacancy-Occupancy
Sensor is available as a vacancy (RVS) or
occupancy (RCS) model, both of which
offer two detection ranges, two radio
frequencies, and can operate using
standard passive infrared (PIR) or Dual
Technology.

The Dual Technology sensor uses PIR and
passive microphone technology to provide
full coverage of audible human activity.
Innovative noise filtering prevents false
triggers that could keep lights on in empty
spaces.

The vacancy ceiling sensor (RVS) has two solar cells to harvest energy
when the lights are ON, while the occupancy ceiling sensor (RCS) is
battery powered to support auto-ON occupancy sensor applications.

Model

Detection

Coverage

RVS-A-xW*

RCS-A-xW*

Lens A: small motion,
short range

42 m

2

at 2.4 m (450 ft

2

 at 8 ft)

74 m

2

at 3.6 m (800 ft

2

at 12 ft)

RVS-B-xW*

RCS-B-xW*

Lens B: large motion,
broad range

167 m

2

at 2.4 m (1800 ft

2

at 8 ft)

279 m

2

at 3.6 m (3000 ft

2

at 12 ft)

RVS-DA-xW*

RCS-DA-xW*

Lens A: small motion,
short range, and audio

42 m

2

at 2.4 m (450 ft

2

at 8 ft)

74 m

2

at 3.6 m (800 ft

2

at 12 ft)

RVS-DB-xW*

RCS-DB-xW*

Lens B: large motion,
broad range, and audio

167 m

2

at 2.4 m (1800 ft

2

at 8 ft)

279 m

2

at 3.6 m(3000 ft

2

at 12 ft)

*Where x is the radio frequency: U=902 MHz and Y=868 MHz.

When used with an Echoflex lighting controller, the sensor is well suited
to meet all energy code requirements for occupancy or vacancy-based
general lighting applications.

This document covers installation, testing, and settings that apply to all
RVS RCS models. The product package includes the sensor, lens mask
stickers, two wire staples, and battery (RCS models only).

Содержание RCS-A-xW Series

Страница 1: ...es The vacancy ceiling sensor RVS has two solar cells to harvest energy when the lights are ON while the occupancy ceiling sensor RCS is battery powered to support auto ON occupancy sensor application...

Страница 2: ...to block off specific areas See Lens Masking on page 5 Do not install within 2 5 m 8 ft of an HVAC airflow duct or vent For the solar powered RVS model before linking the sensor expose it to a good li...

Страница 3: ...uble sided Tape or Velcro 1 Cut two lengths of tape not provided to the appropriate size and adhere one side to the mounting plate and the other to the ceiling 2 Press the sensor firmly in place Sensi...

Страница 4: ...upancy Timer and the controller s Occupancy Timer When the space is vacant and all timers have expired only PIR detection or manual control can change the state to occupied if the sensor is configured...

Страница 5: ...fer to the controller product documentation 3 Press the Teach button on the RVS RCS once to send a message An LED blinks to confirm a successful transmission 4 Deactivate Link mode on the controller b...

Страница 6: ...ructions Light Level Test green LED Range Confirmation blue LED Walk Test red LED Sensor Setting red and blue LEDs LED Display green and red LEDs The menu times out after two minutes of inactivity Lig...

Страница 7: ...inked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach button Walk Test The Walk Test verifies the boundaries or li...

Страница 8: ...nks Occupancy Timer DT model only Note Echoflex dual tech sensors have a configurable Occupancy Timer that sends a vacancy message when expired If using another controller brand with a DT model you ma...

Страница 9: ...when the green and red LEDs are both blinking 3 Press and hold the Teach button until the LEDs stop blinking to select LED Display 4 Press the Teach button to toggle between the two states Red LED bli...

Страница 10: ...io communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipm...

Страница 11: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 11 of 12 Echoflex...

Страница 12: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 12 of 12 Echoflex...

Отзывы: