2.4.2 Modbus RTU control
Use the serial port assistant to control the first DO output of ME31-XAAX0440.
You can test other functions through the commands in the following table.
Function (function code)
Instruction
Pull in the first coil (0x05)
01 05 00 00 FF 00 8C 3A
Full open command (0x0F) 01 0F 00 00 00 04 01 0F 74 92
Full close instruction (0x0F) 01 0F 00 00 00 04 01 00 3E 96
Read all AI inputs (0x04)
01 04 00 64 00 04 B0 16
Read all DO status (0x01)
01 01 00 00 00 04 3D C9
2.5 Host computer control
For details, please refer to "Chapter 5 Host Computer".