ELF INSTALLATION

The ELF is designed for use in smaller ducts (up to 16 inches) and in VAV terminal box applications in an environment
between -20°F to 120°F  (-28.9° C to 48.9° C) where it will not be exposed to rain or snow.  ELF airflow measurement
station sensor probes are designed for insertion mounting through one side of the duct or VAV box.  Mount the instru-
ment in an accessible location to permit set up.  Locate the instrument so that the attached instrument cable will reach
the customer provided BAS control interface.

CAUTION

The installed location of the ELF is critical for proper performance. Refer to the
previous Minimum Placement Guidelines section of this document to
determine the exact location recommended for the ELF.

The installed accuracy of the ELF is ensured in applications where the
maximum inside duct dimension is 16 inches or less.  Applications in larger
duct sizes may degrade accuracy.  Consult factory for these applications.

Ensure that adequate clearance exists to permit insertion of the probe, and to
allow clearance for the instrument enclosure. 

External duct insulation that interferes with mounting should be temporarily
removed prior to installation. Mounting requires a 0.875 inches (22.2 mm)
hole on the insertion side of the duct.

1.

Determine where the ELF airflow measuring station is to be located as indicated on the engineer's plans.

2.

Carefully open the ELF package and inspect for damage.  If damage is noted, immediately file a claim with carrier.

3.

Locate and mark the point on the duct or VAV box where the probe will be inserted, using the previous Minimum
Placement Guidelines section of this document.  Refer to Figures 3 and 4 for ELF dimensions and probe orientation.

4.

Using a 0.875 inches (22.2 mm) hole saw, drill the insertion side hole where marked.

5.

Place the probe through the mounting hole, making sure that the gasket is seated firmly against the integral mount-
ing bracket.  Ensure that the edge of the ELF mounting bracket is parallel to the edge of the duct or VAV terminal
box, and that the airflow arrow printed on it is oriented in the direction of actual airflow.  Ensure that the gasket is
firmly seated against the bracket, and then fasten the mounting bracket at the four mounting holes using appropri-
ate sheet metal screws.

6.

Route the ELF instrument cable to the customer provided BAS interface.  Refer to the following sections of this doc-
ument for instrument set up and operation.

Figure 3. ELF Installation Dimensions

Mounting Bracket Detail View

ELF Sensor Probe/Transmitter Detail Views

Содержание ELF/D Series

Страница 1: ...L STAEFA EQUIVALENT OUTPUT FLOW TEMP WITH FLOW INTEGRATION ELF XXXX D03 DUAL 0 10 2 10VDC ANALOG OUTPUT FLOW TEMP AND NO FLOW INTEGRATION ELF XXXX D04 DUAL 0 5 1 5VDC ANALOG OUTPUT FLOW TEMP AND NO FL...

Страница 2: ...0 SW1 SW4 CONFIG DIP SWITCH SELECTOR 10 ELF D INITIAL START UP NORMAL OPERATION 11 Converting the Analog Airflow Output Signal from Linear to Volumetric flow FPM to CFM 11 ELF MAINTENANCE 11 ELF STAND...

Страница 3: ...output options permits interface to virtually all modern building automation systems BAS EBTRON s proprietary flow loss compensation techniques eliminate inaccuracies typically associated with small d...

Страница 4: ...10 2 10VDC 03 5 1 5VDC or Staefa equivalent airflow or equivalent velocity pressure Output Resolution4 0 015 FS D00 and D03 0 03 FS D01 and D04 versions ORDERING GUIDE Specification Notes 1 Accuracy f...

Страница 5: ...Placement of the ELF is critical for proper operation and accuracy of the airflow measurement station Figure 2 shows minimum placement requirements for the ELF in typical applications Placement is ind...

Страница 6: ...nclosure External duct insulation that interferes with mounting should be temporarily removed prior to installation Mounting requires a 0 875 inches 22 2 mm hole on the insertion side of the duct 1 De...

Страница 7: ...ing flow ring Locate ELF 3 inches minimum upstream of box OR 3 inches minimum upstream of flow ring Boxes with no flow rings Locate ELF 3 inches minimum upstream of box EBTRON ELF Actuator by others V...

Страница 8: ...power and analog output to customer interface as outlined in the follow ing paragraphs Refer to Figure 5 and the following ELF D cable color code descriptions Red 24 VAC power Black Common ELF Power...

Страница 9: ...2 10VDC ON and use an R1 value of 500 ohms at the BAS control input interface to produce a corresponding control signal of 4 20mA Similarly for an ELF xxxx D01 or D04 version 0 5VDC set SW2 for 1 5VD...

Страница 10: ...VALENT VELOCITY PRESSURE SW2 O 10VDC or 2 10 VDC ANALOG OUTPUT SELECT SW3 SW4 AIRFLOW OUT SCALE See Detail below NOTE CONFIG switches S1 S4 are not active on D02 Staefa model CONFIG DIP Switch Detail...

Страница 11: ...ds and OFF for 2 seconds 9 Confirm that the BAS is receiving the analog output signals that indicate instrument airflow or equivalent velocity pressure and temperature 10 Replace the ELF electronics e...

Страница 12: ...TM_ELF D_R1C EBTRON Inc 1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com...

Отзывы: