Ebtron ELF/D Series Скачать руководство пользователя страница 4

TM_ELF-D_R1C

ELF - E

LECTRONIC

L

OW

F

LOW

A

IRFLOW

/T

EMPERATURE

M

EASUREMENT

ELF 

DUAL ANALOG OUTPUT

/D 

SERIES

EBTRON

, Inc. 1663 Hwy. 701 S., Loris SC 29569 

• 

Toll Free: 800.2

EBTRON

(232.8766) 

• 

Fax: 843.756.1838 

• 

Internet: 

EBTRON

.com

4

SPECIFICATIONS

General

Power Requirement: 24 VAC (22.8 to 26.4 VAC)
Power Consumption: 5 VA max.
Airflow Accuracy: ±3% of reading typical, 0 to 3,000 FPM

1

Temperature Accuracy: ± 0.15° F (0.08°C)
Repeatability: ±0.25% 
Airflow Ranges Available

1

:

0 to 500 FPM [0 to 2.54m/s]
0 to 1,000 FPM [0 to 5.08m/s]
0 to 2,000 FPM [0 to 10.16m/s]
0 to 3,000 FPM [15.24m/s]
0 to 0.05 inches water column (WC) (12.45 Pascal)
0 to 0.15 inches WC (37.36 Pascal).
0 to 0.25 inches WC (62.27 Pascal)
0 to 0.5 inches WC (124.5 Pascal)

Operating Temperature Range (transmitter): 

-20°F to 120°F [-28.9°C to 48.9°C]

Operating Temperature Range (sensor probe):

30°F to 160°F [-1.1°C to 71.1°C]

Operating Humidity Range: 

0 to 99% (non-condensing)    

Probe Sizes

Standard Sizes:

4 to 10 inches (101.6 to 254 mm), in 1 inch 
(25.4 mm) increments; and >10 to 16 inches 
(>254 to 406.4 mm), in 2 inch (50.8 mm) increments.

Sensor Probes

Sensor housing: Glass-filled polypropylene 

(Kynar

®

with 316 SS option)

Sensor potting material: Marine grade, waterproof epoxy 
Internal wiring: Kynar® coated copper
Mounting Style: Insertion Mount, with integral 

mounting bracket

Probe Construction:

0.75 inch (19.05 mm) diameter tubing; 
Type 6063 aluminum alloy standard
Type 316 stainless steel optional

Probe Sizes: 4 to 16 in.
Sensing Points per probe: 

2 per probe from 5 to 16 inches; 
1 per probe on 4 inch probes

Probe Configuration (maximum): 

1 Probe x 2 Independent Sensors

Sensor Assembly (each point): 

Bead-in-glass thermistor devices bonded in housing
with waterproof marine grade epoxy

Instrument cable: UL

®

Plenum Rated, PVC jacket; 

3 feet (0.91 m) standard

Output to Host Controls

ELF/D Interface (Analog Output

2

):

Non-isolated 0

3

-10/2-10VDC (0

3

-5/1-5VDC) or Staefa-

equivalent airflow or equivalent velocity pressure.

Output Resolution

4

: 0.015% FS ( /D00 and /D03)

0.03% FS (/D01 and /D04 versions)

ORDERING GUIDE

Specification Notes:  

1

Accuracy for duct sizes up to 16 inches (406.4 mm).  Consult factory for other sizes.

2

Output on /D00 and /D03 is 0-10/2-10VDC; on /D01 and /D04 versions, 0-5/1-5VDC.

3

The minimum analog output in 0-10 or 0-5 VDC modes is typically 30 mV.

4

Resolution is 0.015% FS for 0-10/2-10VDC output and 0.03% FS for 0-5VDC/1-5VDC output. 

-

Blank (no slash) Aluminum Probe
/ SS

Stainless Steel Probe

/ D00

Dual 0-10VDC/2-10VDC Out (Flow + Temp)/0.015% resolution; With Flow Integration

/ D01

Dual 0-5VDC/1-5VDC Out (Flow + Temp)/0.03% resolution; With Flow Integration

/ D02

Dual Staefa SVP Output (Flow + Temp) with Flow Integration

/ D03

Dual 0-10VDC/2-10VDC Out (Flow + Temp)/0.015% resolution; No Flow Integration

/ D04

Dual 0-5VDC/1-5VDC Out (Flow + Temp)/0.03% resolution; No Flow Integration

/ F00

Single 0-10VDC/2-10VDC Out/0.015% resolution; With Flow Integration

/ F01

Single 0-5VDC/1-5VDC Out/0.03% resolution; With Flow Integration

/ F02

Single Staefa SVP Output with Flow Integration

/ F03

Single 0-10VDC/2-10VDC Out/0.015% resolution; No Flow Integration

/ F04

Single 0-5VDC/1-5VDC Out/0.03% resolution; No Flow Integration

/ N01

RS-485 Output

0400    4 inches
0500    5 inches
0600    6 inches
0700    7 inches
0800    8 inches
0900    9 inches
1000  10 inches
1200  12 inches
1400  14 inches
1600  16 inches

Examples:
For a 9 inch duct, single 0-10/2-10VDC Airflow Output and an aluminum probe, specify order code ELF-0900/F00.
For a 9 inch duct, single 0-5/1-5VDC Output and a stainless steel probe, specify order code ELF-0900/F01/SS.
For a 9 inch duct, Staefa SVP single output and an aluminum probe, specify order code ELF-0900/F02.
For a 9 inch duct, RS-485 Output and an aluminum probe, specify order code ELF-0900/N01.
For a 9 inch duct, dual 0-10/2-10VDC analog output with flow integration filter and an aluminum probe, specify order code ELF-0900/D00.

L

/

E

F

Probe Material Options

Features/Options

Probe Sizes (inches)

/

Содержание ELF/D Series

Страница 1: ...L STAEFA EQUIVALENT OUTPUT FLOW TEMP WITH FLOW INTEGRATION ELF XXXX D03 DUAL 0 10 2 10VDC ANALOG OUTPUT FLOW TEMP AND NO FLOW INTEGRATION ELF XXXX D04 DUAL 0 5 1 5VDC ANALOG OUTPUT FLOW TEMP AND NO FL...

Страница 2: ...0 SW1 SW4 CONFIG DIP SWITCH SELECTOR 10 ELF D INITIAL START UP NORMAL OPERATION 11 Converting the Analog Airflow Output Signal from Linear to Volumetric flow FPM to CFM 11 ELF MAINTENANCE 11 ELF STAND...

Страница 3: ...output options permits interface to virtually all modern building automation systems BAS EBTRON s proprietary flow loss compensation techniques eliminate inaccuracies typically associated with small d...

Страница 4: ...10 2 10VDC 03 5 1 5VDC or Staefa equivalent airflow or equivalent velocity pressure Output Resolution4 0 015 FS D00 and D03 0 03 FS D01 and D04 versions ORDERING GUIDE Specification Notes 1 Accuracy f...

Страница 5: ...Placement of the ELF is critical for proper operation and accuracy of the airflow measurement station Figure 2 shows minimum placement requirements for the ELF in typical applications Placement is ind...

Страница 6: ...nclosure External duct insulation that interferes with mounting should be temporarily removed prior to installation Mounting requires a 0 875 inches 22 2 mm hole on the insertion side of the duct 1 De...

Страница 7: ...ing flow ring Locate ELF 3 inches minimum upstream of box OR 3 inches minimum upstream of flow ring Boxes with no flow rings Locate ELF 3 inches minimum upstream of box EBTRON ELF Actuator by others V...

Страница 8: ...power and analog output to customer interface as outlined in the follow ing paragraphs Refer to Figure 5 and the following ELF D cable color code descriptions Red 24 VAC power Black Common ELF Power...

Страница 9: ...2 10VDC ON and use an R1 value of 500 ohms at the BAS control input interface to produce a corresponding control signal of 4 20mA Similarly for an ELF xxxx D01 or D04 version 0 5VDC set SW2 for 1 5VD...

Страница 10: ...VALENT VELOCITY PRESSURE SW2 O 10VDC or 2 10 VDC ANALOG OUTPUT SELECT SW3 SW4 AIRFLOW OUT SCALE See Detail below NOTE CONFIG switches S1 S4 are not active on D02 Staefa model CONFIG DIP Switch Detail...

Страница 11: ...ds and OFF for 2 seconds 9 Confirm that the BAS is receiving the analog output signals that indicate instrument airflow or equivalent velocity pressure and temperature 10 Replace the ELF electronics e...

Страница 12: ...TM_ELF D_R1C EBTRON Inc 1663 Hwy 701 S Loris SC 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 Internet EBTRON com...

Отзывы: