ELF/D INITIAL START UP / NORMAL OPERATION

The following procedure is intended for initial start up of the instrument.  Following the initial set up, no further user activ-
ity is required during normal operation.

1.

Remove the cover to the electronics enclosure by removing the four screws on the cover.

2.

Make sure that the 24VAC circuit breaker used to power the ELF is turned OFF until all wiring is complete!

3.

Confirm 24VAC connection from the power source to the ELF 24VAC wire (red wire) as outlined in the ELF 
24VAC Power Connections section of this document.

4.

Confirm common ground 24VAC and signal ground connection from the power source to the ELF at the black wire.

5.

Confirm ELF/D analog airflow and temperature signal output connections at the white wire and green wire respec-
tively, to the analog input of the BAS as outlined in ELF Analog Output Connections section of this document.  Note
that the ground of the BAS must be at the same voltage reference as the ground of the ELF and the power source.

6.

Set the desired analog output options using CONFIG switches SW1 to SW4 as outlined in the ELF Analog Output
Option Switch Settings section of this document.

7.

Activate the 24VAC power source to power on the ELF.

8.

Following a brief instrument initialization, the green Activity LED will continuously flash ON for 1 second, then OFF
for 1 second.  This indicates normal operation.  In the event of a sensor fault, the LED will produce longer continu-
ous flashes ON for 2 seconds, and OFF for 2 seconds.

9.

Confirm that the BAS is receiving the analog output signals that indicate instrument airflow (or equivalent velocity
pressure) and temperature.

10. Replace the ELF electronics enclosure cover and secure with the four screws removed in step 1.

Converting the Analog Airflow Output Signal from Linear to Volumetric flow - FPM to CFM

The analog airflow output can be converted from velocity (FPM) to an equivalent volumetric flow (CFM) by multiplying the
indicated flow velocity by the free area of the sensor installed location (in square feet).  For example, with an ELF/D00
installed in a 12 inch round duct, using the 0-10VDC scale and 3,000 FPM full scale output range options; an airflow
output of 5VDC indicates a flow velocity of 1,500 FPM (5VDC is one-half of the 0-10VDC output, corresponding to half of
the 0-3,000 FPM scale; and equals 1,500 FPM).  The ELF installed duct location area in this example is calculated at
0.785 ft

2

(using Pi x duct radius

2

, or 3.14 x 0.5ft

2

).  Multiplying the indicated instrument output of 1,500 FPM by the duct

free area of 0.785 ft

2

yields an equivalent volumetric flow of 1,177.5 CFM.

ELF MAINTENANCE

In most HVAC environments, periodic maintenance and calibration is not required or recommended

*

.

*

Depending on the application, it may be necessary to periodically inspect and clean sensors using compressed air or a small brush.  Factory performance returns imme-

diately after cleaning.  Recalibration is NOT required.  Periodic inspection of the sensors is always advised, and accessibility must be considered in these applications.

ELF STANDARD LIMITED PARTS WARRANTY

If any 

EBTRON

product fails within 36 months from shipment, 

EBTRON

will repair/replace the device free of charge as

described in the company’s warranty contained in 

EBTRON

’s Terms and Conditions of Sale.  Defective equipment shall

be shipped back to 

EBTRON

, freight pre-paid, for analysis.

Содержание ELF/D Series

Страница 1: ...L STAEFA EQUIVALENT OUTPUT FLOW TEMP WITH FLOW INTEGRATION ELF XXXX D03 DUAL 0 10 2 10VDC ANALOG OUTPUT FLOW TEMP AND NO FLOW INTEGRATION ELF XXXX D04 DUAL 0 5 1 5VDC ANALOG OUTPUT FLOW TEMP AND NO FL...

Страница 2: ...0 SW1 SW4 CONFIG DIP SWITCH SELECTOR 10 ELF D INITIAL START UP NORMAL OPERATION 11 Converting the Analog Airflow Output Signal from Linear to Volumetric flow FPM to CFM 11 ELF MAINTENANCE 11 ELF STAND...

Страница 3: ...output options permits interface to virtually all modern building automation systems BAS EBTRON s proprietary flow loss compensation techniques eliminate inaccuracies typically associated with small d...

Страница 4: ...10 2 10VDC 03 5 1 5VDC or Staefa equivalent airflow or equivalent velocity pressure Output Resolution4 0 015 FS D00 and D03 0 03 FS D01 and D04 versions ORDERING GUIDE Specification Notes 1 Accuracy f...

Страница 5: ...Placement of the ELF is critical for proper operation and accuracy of the airflow measurement station Figure 2 shows minimum placement requirements for the ELF in typical applications Placement is ind...

Страница 6: ...nclosure External duct insulation that interferes with mounting should be temporarily removed prior to installation Mounting requires a 0 875 inches 22 2 mm hole on the insertion side of the duct 1 De...

Страница 7: ...ing flow ring Locate ELF 3 inches minimum upstream of box OR 3 inches minimum upstream of flow ring Boxes with no flow rings Locate ELF 3 inches minimum upstream of box EBTRON ELF Actuator by others V...

Страница 8: ...power and analog output to customer interface as outlined in the follow ing paragraphs Refer to Figure 5 and the following ELF D cable color code descriptions Red 24 VAC power Black Common ELF Power...

Страница 9: ...2 10VDC ON and use an R1 value of 500 ohms at the BAS control input interface to produce a corresponding control signal of 4 20mA Similarly for an ELF xxxx D01 or D04 version 0 5VDC set SW2 for 1 5VD...

Страница 10: ...VALENT VELOCITY PRESSURE SW2 O 10VDC or 2 10 VDC ANALOG OUTPUT SELECT SW3 SW4 AIRFLOW OUT SCALE See Detail below NOTE CONFIG switches S1 S4 are not active on D02 Staefa model CONFIG DIP Switch Detail...

Страница 11: ...ds and OFF for 2 seconds 9 Confirm that the BAS is receiving the analog output signals that indicate instrument airflow or equivalent velocity pressure and temperature 10 Replace the ELF electronics e...