STARTUP INSTRUCTIONS:  
1.  Verify that the sensor probe is located where they meet EBTRON published installation guides. 
2.  Verify that the probe is properly installed with the airflow arrow pointing in the direction of airflow. 

 

Improperly installed probes will compromise the installed accuracy of the device and degrade system 
performance.

 

3.  Verify that the transmitter is installed and wired in accordance with the 

HTA104-T Wiring Guide

 

provided with the transmitter and power is provided to the transmitter. 

4.  Make sure the ductwork is clean and free of debris prior to fan startup. 
5.  Move the power switch to the “ON” position.  Power-up faults, if detected, are displayed on the LCD.   

If any power up faults are detected, resolve all conflicts or contact EBTRON customer service at        
1-800-232-8766 before proceeding.. 

 

If extension cables have been added, the extension cable length must be entered into the transmitter.  
Refer to the Operations and Maintenance Manual for more information. 

6.  The transmitter is fully functional as a factory calibrated airflow and temperature measurement device 

in I-P units (ft, FPM, CFM °F).  Airflow (CFM) and temperature (°F) are displayed on the LCD. 

 

If SI units are required, refer to the Operations and Maintenance Manual. 

 

 

The factory default airflow output is set to actual airflow (FPM, CFM).  If standard (mass) airflow 
(SFPM, SCFM) is required, refer to the Operations and Maintenance Manual. 

7. 

Verify that the area on the hang-tag matches the actual area of the duct or opening where the probes 
are located (less any internal insulation).  If the area is different, modify the area parameter stored in 
the transmitter and use the correct area for any external conversion calculations from FPM to CFM.

   

 

Failure to use the correct area will result in volumetric airflow (CFM) measurement error and degrade 

Advantage IV (A4) HTA104-T STARTUP GUIDE 

Description

Parameter Default

Optional Settings/Ranges

Units

System of Units

SYS

I-P (US customary) SI (metric)

Airflow Calculation Method

AIRFLOW

ACT (actual)

STD (standard mass flow)

Altitude (for actual flow correction) ALT

0

0 to 20000 [0 to 6000]

ft [m]

Low Limit Airflow Cutoff

LLIMIT

0 FPM

0 to 500 FPM [0.0 to 2.5 m/s]

Area

AREA

{Order Area}

0.00 to 9999.99 [0.000 to 999.999]

sq ft [sq m]

AO1 Type

AOUT1

4-20mA

0-10V, 0-5 V

AO2 Type

AOUT2

4-20mA

0-10V, 0-5 V

AO1 Assignment

AO1 ASGN AF (Airflow)

None

AO1 Unit of Measure

AO1 UM

FPM [m/s]

CFM [L/s]

AO1 Minimum Scale Reading

AO1 MS

0

None

FPM [m/s]

AO1 Full Scale Reading

AO1 FS

3000 [15.0]

100 to 15000 [0.5 to 75.0]

FPM [m/s]

AO2 Assignment

AO2 ASGN TEMP (Temperature) ALRM (Alarm) or TRBL (System Trouble)

AO2 Unit of Measure

AO2 UM

F [C]

None

°F

 

[°C]

AO2 Minimum Scale Reading

AO2 MS

-20 [-30]

-50 to 160 [-50 to 70]

°F

 

[°C]

AO2 Full Scale Reading

AO2 FS

160 [70]

-50 to 160 [-50 to 70]

°F

 

[°C]

HTA104-T Parameters - Factory Defaults and Optional Settings/Ranges

Refer to the O&M Manual for more information and/or additional parameter defaults, settings and ranges. 