31
Start-Up
16.3.1 Basic settings of the process controller
→
In the main menu (MAIN) select the P.CONTROL function and
make the basic settings.
EXIT
ENTER
16
M A I N
P.CONTROL
ADD.FUNCTION
P.TUNE
EXIT
EXIT
PID.PARAMETER
SETUP
DBND 0,1 %
PV-INPUT
KP 0,00
PV-SCALE
TN 0,5
SP-INPUT
TV 0,0
SP-SCALE*
X0 0,0 %
P.CO-INIT
FILTER 0
P.CONTROL
ENTER
ENTER
ENTER
EXIT
Main menu
* The SP SCALE function
appears only when the
external preselected set-
point value (external) menu
option is activated under
SP INPUT.
Fig. 16: Operating structure - basic settings of the process controller
P.CONTROL
- settings:
PID.PARAMETER
Parameter settings of the process controller
DBND 0,1 %
Insensitivity area of the PID process controller
KP 0,00
Amplification factor of the process controller
TN 0,5
Reset time
TV 0,0
Hold-back time
X0 0,0 %
Operating point
FILTER 0
Filtering of the process actual value input
SETUP
Setting up the process controller:
PV-INPUT
AIndication of the signal type for process
actual value
PV-SCALE
Scaling the process controller
SP-INPUT
Type of the set-point value default (internal or
external)
SP-SCALE*
Scaling the position controller (for external set-
point value default only)
P.CO-INIT
Enables a smooth switchover between AUTO-
MATIC and MANUAL operating state
Tab. 13: Basic settings of the process controller
Parameters can be set automatically with the aid of the
P.TUNE
function (description see “Operating instructions for Type EP
501”).
english
Type EP 501
Содержание EP 501
Страница 95: ...www ebro armaturen com...