Auxiliary functions
24.2.15.
CAL.USER –
Calibration of actual value and set-point value
The following values can be manually calibrated with this function:
• Position actual value
calibr. POS
(0 - 100 %)
• Position set-point value
calibr. INP
(4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)
For the calibration process the signal type is displayed which was specified for the input signal.
See Chapter “21.1. INPUT - Setting the input signal”.
Type.EP.501.C:
The following values can be calibrated only for Type EP 501 C and activated process controller (
P.CONTROL
).
• Process set-point value
calibr. SP
(4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)
For the calibration process the signal type is displayed which was specified for the input signal.
See Chapter “21.1. INPUT - Setting the input signal”.
The calibration of the process set-point value is only possible if the external set-point value default was
selected when setting up the process controller.
See Chapter “23.2.3. SP-INPUT – Type of the set-point value default (intern or extern)”.
Setting:
P.CONTROL
→
SETUP
→
SP-INPUT
→
external
• Process actual value
calibr. PV
(4 - 20 mA or *C)
For the calibration process the signal type is displayed which was specified for the process actual value when
setting up the process controller.
See Chapter “23.2.1. PV-INPUT – Specifying signal type for the process actual value”
The frequency signal type (flow rate) cannot be calibrated.
If the frequency was set when setting up the process controller (
P.CONTROL
→
SETUP
→
PV-INPUT
→
Frequency)
, the
calibr. PV
menu option is hidden.