3.2 Nominal data

Motor

M4D110-EF

Phase

3~

Nominal voltage / VAC

400

Wiring

Δ

Frequency / Hz

50

Method of obtaining
data

ml

Valid for approval/
standard

CE

Speed (rpm) / min

-1

1350

Power consumption / W

710

Current draw / A

1.4

Max. back pressure / Pa

170

Min. ambient
temperature / °C

-40

Max. ambient
temperature / °C

40

Starting current / A

4.6

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

38

32.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

45.3

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

W4D500-KJ03-01

09 Power consumption P

e

/ kW

0.7

09 Air flow q

v

/ m³/h

5745

09 Pressure increase total p

fs

/

Pa

168

10 Speed (rpm) n / min

-1

1345

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

12.58 kg

Size

500 mm

Motor size

110

Rotor surface

Painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Fan housing material

PP plastic

Material guide vanes

PP plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Ambient temperature
note

If there is a risk of ice formation, the fan
is only to be operated with a heating tape
in the fan housing. Further information
can be obtained from ebm-papst. As fan
only suitable for use with industrial
evaporators

Installation position

See fitting instructions

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing with low-temperature lubricant

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) with
basic insulation

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60034-1 (2010); CE

Approval

VDE; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

Item no. 15825-5-9970 · ENU · Change 230069 · Approved 2021-05-19 · Page 6 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W4D500-KJ03-01

Страница 1: ...zed technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety...

Страница 2: ...he fan to be able to get past the fan 1 6 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidenta...

Страница 3: ...g the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe v...

Страница 4: ...duct drawing All dimensions in mm 1 Airflow direction V 2 Cable silicone 6G 0 5 mm 6x wire end ferrule Item no 15825 5 9970 ENU Change 230069 Approved 2021 05 19 Page 4 13 ebm papst Mulfingen GmbH Co...

Страница 5: ...ort struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 15825 5 9970 ENU Change 230069 Approved...

Страница 6: ...vanes PP plastic Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Airflow direction V Direction of rotation Counterclockwise viewed toward rotor Degree of protection...

Страница 7: ...l box kit provides an ideal means of connecting the electrical connections of the motor heating tape and drip pan The terminal box kit to suit the AxiCool fan housing and motor is available from ebm p...

Страница 8: ...vice voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must ha...

Страница 9: ...stalled in the winding The motor is provided with a thermal overload protector TOP Always check that the thermal overload protector TOP is properly connected before start up Failure to connect the the...

Страница 10: ...nge of rotation direction by reversing two phases Delta connection L1 blue L2 black L3 brown TW Thermal overload protector gray 2x PE green yellow Item no 15825 5 9970 ENU Change 230069 Approved 2021...

Страница 11: ...switch When disconnecting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm paps...

Страница 12: ...e 5 2 Safety inspection What to check How to check How often What action Contact protection cover for intactness or damage Visual inspection At least every 6 months Repair or replacement of device Dev...

Страница 13: ...xternal rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...