53
03/15 MN03407004Z-DE/EN
3
Installation
Installation instructions
The mechanical and electrical instruction leaflet must be
observed.
The instruction leaflet is printed on the inside of the
cardboard packaging.
h
ZB12/XTOB…BC1, ZB32/XTOB…CC1
The AWA2300-2114 instruction leaflet has been renamed
to IL03407015Z as of publication date 10/10.
h
ZB32-38
The IL3407082Z instruction leaflet applies to the
ZB32-38… overload relay.
j
Danger!
To ensure explosion-proof operation, the motor-protective
relay may only be reset/switched on manually, or
automatically via a control interlock circuit for the motor
or electrical machinery, after the bimetallic release has
cooled down.
Resets may be carried out at the installation or by trained
personnel in the control room.
j
Danger!
Particularly in Ex e applications, an automatic restart must
be prevented after an interruption of the control voltage.
This is prevented safely by means of the latching function
of the power relay.
Содержание ZB12/XTOB BC1 Series
Страница 10: ...6 03 15 MN03407004Z DE EN...
Страница 26: ...22 03 15 MN03407004Z DE EN...
Страница 40: ...36 03 15 MN03407004Z DE EN...
Страница 56: ...52 03 15 MN03407004Z DE EN...