4 Installation
4.6 Connecting the power supply
XP-503 04/2020 MN048014 EN Eaton.com
27
4.6
Connecting the power supply
Before connecting the power supply
CAUTION
Control required
Does the voltage fall within the permissible input range?
Functional earth: Connect the earth point to the cabinet's earth!
M6 x 12 earthing stud on the back of the display housing
Supply voltage 24 V DC
CAUTION
Safety extra-low voltages (SELV) necessary
24 V DC (18 – 36 V DC) supply for integrated DC/DC converter.
The applied voltage must meet the requirements for safety extra-low voltages
(SELV) set forth in IEC 60950 and – in connection with the UL listing – the
requirements for a low-voltage source set forth in UL 508!
Pay attention to the polarity!
Example: XP-503-15
The following also applies to other device versions as applicable.
Bottom of housing:
Fig. 7
Connecting the 24 V DC supply voltage
Connection cable
For the power supply connection:
Copper conductor:
60° / 70°C
Cross section:
0.75 – 2.5 mm²
Tightening torque
of 0.56 to 0.79 Nm (screws on plug section)