4 Technical Features
4.6 Storing the station configuration
44
XI/ON: XNE-GWBR-2ETH-MB
10/2011 MN05002008Z-EN
www.eaton.com
4.6
Storing the station configuration
4.6.1
DIP-switch CFG
The DIP-switch "CFG" at the gateway serves to take-over the Current Configuration of the
XI/ON-station as Required Configuration to the gateway’s non-volatile memory.
Switching from OFF to ON starts the storage of the Current Configuration as the Required
Configuration (Reference configuration).
Procedure:
Switching the DIP-switch "CFG" from OFF to ON
→
Starting of the storage process
→
LED IOs flashes green (1 HZ)
→
LED IOs shortly lits up orange
→
storage process active
→
set back the DIP-switch from ON to OFF
→
storage process terminated successfully, if the LEDs IOs and GW are constant green.
Figure 31:
DIP-switch for
storing the
station configu-
ration
Note
If the DIP-switch is not set back, the gateway will continiously restart the storage
process. Only setting the switch back from ON to OFF will terminate this process.