4 Functions of the count inputs (CNT1 and CNT2)
4.1 Basic functions of the count inputs CNTx
XI/ON: XNE-2CNT-2PWM
04/2011 MN05002035Z-EN
www.eaton.com
47
Special function Zx (CNT): alarm
If Zx is parameterized as alarm signal for the counter (Parameter data of the module (page 25)),
then the signal status is reported as message.
→
Enable/disable the special function (
→
see page 45)
After an alarm signal occurred, bit MSG_CNTx_SFKT page 28 in the Process input / check-back
interface is set.
Special function Zx (CNT): HW gate
→
Enable/disable the special function (
→
see page 45)
If Zx is parameterized as HW gate for the counter (Parameter data of the module (page 25)),
the counter gate is enabled with Zx = 1, and disabled with Zx = 0.
Note
When using alarm-signals as Open Collector, a pull up resistance can be switched
via the Parameter data of the module (page 25).
Note
Enabling the counter can be done either via the hardware
or
the software gate.
Please read Enabling the counter (page 37).