23 Analog input module XN-322-10AI-TEKT
23.3 Memory layout
172
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
23.3 Memory layout
Cold-junction compensation can be implemented by using the KTY channels.
To do this, the parameters must be configured in such a way as to assign a
KTY channel to each measuring channel for compensation purposes.
Measuring ranges are configured using a single byte for the two channels in
each Xn connector. For example: The measuring range for 1+ and 2+ is con-
figured using object 0x50A0, where the high nibble is used to configure 1+
and the low nibble is used to configure 2+.
L
Fe-CuNi
0…+680 °C
U
Cu-CuNi
0…+590 °C
KTY10
–
-20 °C… +80 °C
1367…2980
Ω
Type
Thermocouple
Measuring range
resistor
CAN Object
Index
Size
(byte)
Description
Bit
AI
Description
30A0
2
Modules Diagnostics
Bit 0
reserved
Bit 1
No SYNC signal
Bit 2
FLASH-CRC error
Bit 3
RAM-CRC error
Bit 4
Flash memory
error
Bit 5-15
reserved
30A1
6401
2
Temperature reading 1 (AI1)
AI1
30A2
6401
2
Temperature reading 2 (AI2)
AI2
30A3
6401
2
Temperature reading 3 (AI3)
AI3
30A4
6401
2
Temperature reading 4 (AI4)
AI4
30A5
6401
2
Temperature reading 5 (AI5)
AI5
30A6
6401
2
Temperature reading 6 (AI6)
AI6
30A7
6401
2
Temperature reading 7 (AI7)
AI7
30A8
6401
2
Temperature reading 8 (AI8)
AI8
30A9
6401
2
Reference input KTY 1 for
cold-junction compensation
KTY1
30AA
6401
2
Reference input KTY 2 for
cold-junction compensation
KTY2