3 Commissioning
3.1 Take system bus into operation
42
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
3.1.1.1 In operation
Regardless of the config check setting, the gateway will check whether the
actual configuration changes during operation.
If there are any configuration changes during operation, the gateway will be
reset.
One possible cause of a configuration change is when a part of the system
block becomes disengaged on purpose or by accident. Another possible
cause is a module that has dropped out from the system bus.
Depending on whether the config check function is enabled or disabled, the
gateway will either start with the modified configuration (config check dis-
abled) or will stay in safe mode (config check enabled – check failed).
Yes
No
I/O LED green, continuous light
Error on system bus
Software-controlled RESET
Device running
I/O LED green, flashing
Yes
No
ON
OFF
→
Figure 23
=
Last station
Responds
Additional module
after
last module
DIP switch 9
Config check