2 Installation
2.9 Connect diagnostics interface
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
37
It may be necessary to use repeaters when using cable lengths of 1,000 m or
more.
2.9 Connect diagnostics interface
The gateway features a Mini-USB port on the front. By using a programming
cable, you can connect it to a computer and do the following with the corre-
sponding software:
•
Use the XN300-Assist program to run real-time diagnostics on the sys-
tem bus
•
Updating the operating system
You can use any of the following programming cables:
USB 2.0 cable: Mini-B connector <-> Type A connector
2.10 Connection example
Figure 23:
Connecting example for XN-312-GW-CAN gateway in XN300 system
100
650
125
500
250
250
500
100
800
50
1000
25
Baud rate (kBaud)
Maximum cable length (m)
24 V DC
V+
0 V
V+
0 V
GND
PE
system bus
0 V
U
BP_24V
+24 V DC
U
BP_5V
+5 V DC
U
POW
X3
XN-312-GW-CAN
UL: F1 ≦ 2 A
IEC: F1 ≦ 3 A
XN-322
IEC/EN 60715
XN-322
≦ 31 x XN-322