7 Product-specific CAN objects XN300 slice modules
7.23 XN-322-2DMS-WM
306
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.23.2 Input Channel x (Object 0x3061 to 0x3062)
Objects 0x3061 to 0x3062 represent the analog input values
Design of the data bytes:
Feature
Description / Value
EDS
Name
Channel1Input
Object 0x3061
[MxSubExt306x]
ParameterName=ChannelxInput
ObjectType=0x7
DataType=0x0004
AccessType=ro
PDOMapping=1
Count=1
Channel2Input
Object 0x3062
Description
Input Channel x
Object Code
ARRAY
Mapping
PDO
Manual
Data type
INTEGER32
Sub index
01 … FE
hex
Access
ro
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
LSB
4 Byte
3 Byte
Sub index
1
≦
n
≦
254
B31
B30
B29
B28
B27
B26
B25
B24
B23
B22
B21
B20
B19
B18
B17
B16
MSB