7 Product-specific CAN objects XN300 slice modules
7.14 XN-322-4AI-PTNI
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
175
7.14.11 Wire Break Diagnostic Messages (Object 0x3075)
Object 3075 contains status information on the module's channels.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
WireBreakDiag
[MxSubExt3075]
ParameterName=WireBreakDiag
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=1
Description
Wire Break Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
7
6
5
4
3
2
1
0
–
–
CLASS
CLASS
CLASS
TYPE
TYPE
TYPE
Data bit
Desig-
nation
Description
Notes
0
0 = Channel 1 OK
1 = Channel 1 wire breakage
1
0 = Channel 2 OK
1 = Channel 2wire breakage
2
0 = Channel 3 OK
1 = Channel 3 wire breakage
-
3
0 = Channel 4 OK
1 = Channel 4 wire breakage
4 – 7