Eaton Vickers CM2 Series Скачать руководство пользователя страница 7

7

Section III 

 Principles of Operation 

A. General 

Figure 2 is a schematic illustration of a four section valve,
showing the cylinder ports and the by-pass pressure and
tank passages. The pressure passage is used to carry fluid
to the cylinder ports when the spools are shifted. The by-
pass passage permits flow directly to the outlet when the
spools are not being operated. The tank passages carry fluid
to the tank port by return flow from the cylinder ports or fluid
diverted past the flow control and relief valve.

The spools are shown in the centered or neutral position.
Under these conditions, fluid in the pressure passage is
blocked from the cylinder ports by the spool lands. Flow
through the valve is through the by-pass and tank passage
to the tank port.

B. Operating Sections 

1. 

Inlet Section

 - The CM2 and CM3 series valve banks

may be obtained with operating, R*, F*, or K*, inlet sections.
These sections are available with B, C, D, or T, type spools. 

These sections are individually described below.

a. 

R* Section

 - The R* section is equipped with an

integral relief valve for overload protection. It is built to accept
a check valve to prevent return flow through the valve.

The integral relief valve, with an orifice plug, also

acts as a partial flow control valve. This feature lowers the
pressure drop between the inlet and outlet ports. (See para-
graph 4 for relief valve and flow control operation.)

The relief valve cracking pressure is pre-set at the

factory. The pre-set cracking pressures range up to 2500 psi
maximum. (See Table 2 Model Code for pressure settings.)

b. 

F* Section

 - The F* section has two pressure

connections. One connection is made to the pump source
and the second connection is made with a preceding valve
assembly to accept the by-pass flow for tandem operation.

    The F* section like the R* section is built to accept

a check valve to prevent return flow when this feature is
required. However, F* sections do not employ relief valve or
partial flow by-pass.

c. 

K* Section

 - The K* section is essentially the same

as the R* section except it has a full flow by-pass feature.

2. 

Outlet Sections 

a. 

*L Section

 - When two or more spools are required

in a valve bank, the last section will be an *L section. The 

*

denotes the spool type. This section contains the exhaust oil
port and also is built to accept a check valve to prevent back
flow when this feature is required.

b. 

*E Section

 - This section is used for tandem

operation by providing an outlet connection through which
the by-pass feature for pump unloading is extended on to a
subsequent valve bank. It is used in conjunction with an 

F*

type inlet section in the next valve bank. Like the *L section it
contains an operating spool and is built to accept a check
valve to prevent back flow when this feature is required.

3. 

Spool Operation 

General

 - Four standard spool designs are available

(

B, 

 

C,

 

D,

 or 

T,

). Any combination of spools may be

used with a valve bank to perform a variety of operations. All
operating spools are equipped with centering springs which
return the spools to neutral.

Figure 2.

Check Valve

Flow Control &

Relief Valve

Cylinder Ports

B

 Spool

Control Valve 

Sensing Orifice

Out

Neutral

In

Out

Neutral

In

Out

Neutral

In

Out

Neutral

In

C

 Spool

D

 Spool

T

 Spool

Float

Relief Valve

Tank Passage

Tank Passage

Tank

Port

By-Pass

Carry over Port

Cap

A

B

A

B

Pressure

Tank Passage

Pressure

Port

By-Pass

Flow Control

Orifice

A

B

Содержание Vickers CM2 Series

Страница 1: ...M 2400 S Revised 7 1 86 Multiple Unit Valves CM2 and CM3 Series 20 Design CM2 and CM3 Series 30 Design Overhaul Manual Vickers Directional Controls...

Страница 2: ...ferenced in Table I be consulted for service parts for the respective design Customers who wish to incorporate 30 design sections in 20 design valves can do so without concern In this instance a tie b...

Страница 3: ...6 Detent 9 7 Tandem Operation 10 C Non Operating Sections 10 1 General 10 IV Installation 11 A Installation Drawings 11 B Mounting 11 C Port Connections 11 D Relief Valve 11 E Tandem Installation 11 F...

Страница 4: ...mensions are not contained in this manual The parts catalogs and installation drawings listed in Table 1 are available from your local Vickers Mobile Division application engineering office or from Vi...

Страница 5: ...ions Table 2 Model Code Breakdown 4 Port Connections CM2 Series 1 1 3 16 12 inlet cyl ports 1 5 16 12 outlet ports 2 1 5 16 12 inlet cyl ports 1 5 8 12 outlet ports 4 1 5 8 12 inlet outlet ports 1 5 1...

Страница 6: ...and a check valve The inlet section also contains a relief valve assembly Passages between the bodies connect each section to the common inlet and tank ports Seal rings between the sections seal the...

Страница 7: ...has two pressure connections One connection is made to the pump source and the second connection is made with a preceding valve assembly to accept the by pass flow for tandem operation The F section l...

Страница 8: ...he end of the cylinder not under pressure has its return flow directed to tank via internal coring of the valve sections See Figure 5 for spool position versus flow D Double Acting Spool B A P T MAN M...

Страница 9: ...s the opposite end The valve is thus hydrau lically balanced and the large spring holds it closed Figure 6 Neutral Out Pressure Tank Return Flow A T spool in OUT position Pressure to B port A port blo...

Страница 10: ...second bank Otherwise reduced flow will be encountered C Non Operating Sections 1 General The CM2 valve non operating sections are the E and L outlet sections and a center U section These sections do...

Страница 11: ...s are nec essary for proper installation should be used G Hydraulic Fluid Recommendations The oil in a hydraulic system serves as the power transmission medium It is also the system s lubricant and co...

Страница 12: ...oil should not be less than 90 Multiple viscosity oils such as SAE 10W 30 incorporate additives to improve viscosity index polymer thickened Oils of this type generally exhibit both temporary and per...

Страница 13: ...reign particles If excessive contamination is found the system should be drained The reservoir must be cleaned thoroughly before refilling C Adding Fluid to the System When hydraulic fluid is added to...

Страница 14: ...detent barrel Weak or broken detent spring Replace detent barrel Replace detent spring No motion slow or jerky action of hydraulic system Relief valve not properly set or stuck in base and or worn Di...

Страница 15: ...akage the surfaces can be stoned or polished with crocus cloth If scoring is excessive the valve body and spool must be replaced by ordering a new section Check the valve spool for freedom of movement...

Страница 16: ...function when the spool is in neutral and oper ating position 2 Anti Cavitation Check with Cylinder Port Relief Valve The anti cavitation check with cylinder port relief valve is a combination of ant...

Страница 17: ...ainer 2 req d Spring Guide Cap Screw 2 Req d Screw Body and spool not availabel separately Order valve seciton by model number Ring Ring 4 req d Plug O Ring Spring Control Valve Sub Assy Plug Not used...

Страница 18: ...tion Detent used on I Section F Inlet Section U Section L Section Plug Spring Piston Cap Screw Screw 2 req d Detent Plug O Ring Spring Guide Ball Cap O Ring Spring Cylinder Port Relief Valve Subassemb...

Страница 19: ...All rights reserved Printed in U S A Eaton Hydraulics 15151 Highway 5 Eden Prairie MN 55344 Telephone 612 937 7254 Fax 612 937 7130 www eatonhydraulics com 46 New Lane Havant Hampshire PO9 2NB Englan...

Отзывы: