Parameters —
M
1
Standard Parameters —
M
1
Parameter value ca
n
o
n
ly be cha
n
ged after the drive has bee
n
stopped.
Code
Parameter
M
in.
M
ax.
Unit
Default Cust ID
Note
P1.1.1
Mi
n
freque
n
cy
0.00
Par.
1.1.2
Hz
0.00
101
P1.1.2
Max
freque
n
cy
Par.
1.1.1
320.00 Hz
60.00
102
NOTE
: If f
max
>
tha
n
the motor
sy
n
chro
n
ous
speed, check
suitability for
motor a
n
d drive
system.
P1.1.3
Acceleratio
n
time 1
0.1
3000.0 s
3.0
103
P1.1.4
Deceleratio
n
time 1
0.1
3000.0 s
3.0
104
P1.1.5
Curre
n
t limit
0.1 x
I
H
2 x I
H
A
I
L
107
P1.1.6
Nomi
n
al
voltage of
the motor
180
690
V
P: 230V
P: 460V
P: 575V
110
P1.1.7
Nomi
n
al
freque
n
cy of
the motor
30.00 320.00 Hz
60.00
111
Check the rati
n
g
plate of the
motor.
P1.1.8
Nomi
n
al
speed of the
motor
300
20 000 rpm
1720
112
The default applies
for a 4-pole motor
a
n
d a
n
omi
n
al
size freque
n
cy
co
n
verter.
P1.1.9
Nomi
n
al
curre
n
t of the
motor
0.1 x
I
H
2 x I
H
A
I
H
113
Check the rati
n
g
plate of the
motor.
P1.1.10
Power Factor 0.30
1.00
0.85
120
Check the rati
n
g
plate of the
motor.
P1.1.11 Local Co
n
trol
Place
1
3
2
171
1
=
I/O Termi
n
al
2
=
Keypad
3
=
Fieldbus
P1.1.12 Remote
Co
n
trol
Place
1
3
1
172
1
=
I/O Termi
n
al
2
=
Keypad
3
=
Fieldbus
P1.1.13
Local
refere
n
ce
0
3
2
173
0
= AI1
1
= AI2
2
= Keypad
3
= Fieldbus
P1.1.14
Remote
refere
n
ce
0
3
0
174
0
= AI1
1
= AI2
2
= Keypad
3
= Fieldbus
P1.1.15 Ide
n
tificatio
n
0
2
0
631
0
= Not used
1
= V/Hz
2
= V/Hz with
boost
P1.1.16 V/Hz Opt
0
1
0
109
0
= Not used
1
= Automatic
torque boost
P1.1.17 Preset
speed 1
0.00
Par.
1.1.2
Hz
10.00
105
S
peeds preset by
operator.
P1.1.18 Preset
speed 2
0.00
Par.
1.1.2
Hz
40.00
106